チウムイオン蓄電システム 太陽光エネルギー
Solar energy storage application
Integrate mains power and solar energy storage systems to provide emergency power backup and peak power adjustment to achieve the purpose of saving electricity bills and reducing contract power.
It can also meet the energy storage construction requirements of large power consumers.
Inverter | Model | SP40K Giant |
SP60K Giant |
SP80K Giant |
SP100K Giant |
SP120K Giant |
|
Rated power | 40KVA 36KW |
60KVA 54KW |
80KVA 72KW |
100KVA 90KW |
120KVA 108KW |
||
Input | Voltage | 380VAC ± 20% | |||||
Frequency range | 50 / 60Hz ± 5Hz (Can be set) | ||||||
Max. efficiency DC/ AC |
92% | 93% | |||||
Output | AC voltage regulation (battery mode) |
380VAC ± 1% | |||||
Output frequency | 50 / 60Hz ± 1% (Automatic induction) | ||||||
Highest perf. |
92% | 93% | |||||
Conversion time | 0ms | ||||||
Wave pattern | Pure sine wave | ||||||
Crest factor | 1:3 | ||||||
Overload capacity | ≧105%-110% Lasts 1 hour; ≧110%-125% Lasts 10 minutes;125%-150% Lasts 1 minute; 150% Shuts down in 10 seconds;200% Shuts down now |
||||||
Battery | Battery voltage | 360Vdc | |||||
Float charge voltage | 410Vdc (Default value) | ||||||
Average charge voltage | 415Vdc (Default value) | ||||||
Shutdown voltage | 315Vdc | ||||||
Max. solar charging current | 120A | 180A | 240A | 300A | 360A | ||
Max. mains charging current | 50A | 75A | 160A | 200A | 250A | ||
Solar charger & AC charger | PV max. input power | 25KW x2 |
25KW x3 |
25KW x4 |
25KW x5 |
25KW x6 |
|
PV module slot | 3 | 4 | 6 | 8 | |||
PV array max. open circuit voltage | 750Vdc | ||||||
MPPT operating voltage range | 400 - 450 Vdc | ||||||
PV input current | 120A | 180A | 240A | 300A | 360A | ||
Highest conversion efficiency | 98.00% | ||||||
Exterior | Dimensions (WxDxH)mm | 600 x 700 x 1750 | 960 x 800 x 1700 | ||||
Package dimensions (WxDxH)mm | 690 x 790 x 1850 | 1040 x 890 x 1750 | |||||
Weight (Kg) | 430Kg | 515Kg | 760Kg | 800Kg | 860Kg | ||
Comm. | Comm. port | RS232/ RS485/ SNMP (Optional) | |||||
Dry contact | Overload / Low battery Voltage / Bypass / Fault | ||||||
Operating env. |
Humidity | 10% - 90% (No condensation) | |||||
Operating temp. | 0℃ - 40℃ | ||||||
Height | Rated power is reduced by 1% for every 100m, maximum 4000m | ||||||
IP rating | IP20 | ||||||
Noise | 65dB | ||||||
Battery | Battery composition | 7 Battery modules & 1 Control box | |||||
Number of battery strings | 112S1P (0.5C Std. charge and discharge) | ||||||
Rated capacity | 100Ah | ||||||
Rated voltage | 358.4V | ||||||
Std. discharge current | 50A (0.5C) | ||||||
Max. continuous discharge current | 100A (1C) | ||||||
Cycle life | 1000次@1C, 100%DOD, 35℃ | ||||||
Operating temp. | Charge | 15 - 35℃ | |||||
Discharge | 0 - 45℃ | ||||||
Storage | -30 - 60℃ | ||||||
Battery cabinet dimensions (WxDxH)mm | 600 x 800 x 2000mm | ||||||
Thermal design | Natural heat dissipation ; Noiseless | ||||||
Weight (Kg) | 460Kg |